Rated voltage (kV) |
|
| Insulation level
(kV) |
| Lightning impulse withstand
voltage |
| Power frequency withstand
voltage |
|
| 325 |
450 |
550 |
650 |
750 |
| 140 |
185 |
230 |
275 |
325 |
|
| Circuit Breaker |
| Type |
| Rated current (A) |
| Rated short-time current (kA) |
| Rated interrupting current
(kA) |
| Rated interrupting time
(cycles) |
| Operating mechanism |
|
| Single-pressure
puffer |
| 1250/2000/3150 |
| 25/31.5/40 |
| 25/31.5/40 |
| 3/5 |
| Spring or
pneumatic |
|
| Disconnector
(isolator)1 |
| Type |
| Rated current (A) |
| Rated short-time current (kA) |
| Operating mechanism |
|
| Linear Break |
| 1250/2000/3150 |
| 25/31.5/40 |
| Manual, motor
or pnumatic |
|
| Earthing (grounding
switch) |
| Type |
| Rated short-time current (kA) |
| Operating mechanism |
|
| Linear Break |
| 25/31.5/40 |
| Manual,
motor-charged spring, or pneumatic |
|
| Voltage (potential)1
transformer |
| Type |
| Rated primary voltage (kV) |
| Rated secondary voltage (V) |
|
| Wound |
| 72.5/Ö3 |
100/Ö3 |
123/Ö3 |
145/Ö3 |
170/Ö3 |
|
| 110/Ö3 | 115/Ö3 | 120/Ö3 |
200/Ö3 |
|
| Current transformer |
| Type |
| Rated primary current (A) |
| Rated secondary current (A) |
|
| Troidal (ring)
core |
| 600/750/1000/1250/1500/2000/2500/3000 |
| 1/5 |
|
| Surge arrester |
| Type |
| Rated voltage (kV)2 |
| Rated discharge current (kA) |
|
| Metal Oxide
(MOA) |
| 60/84 |
84/102 |
96/126 |
120/150 |
144/186 |
|
| 10 |
|
| Busbar |
| Enclosure |
| Rated current (A) |
| Rated short-time current (kA) |
|
| Three-phase |
| 1250/2000/3150 |
| 25/31.5/40 |
|
| |
Rated voltage (kV) |
|
| Insulation level
(kV) |
| Lightning impulse withstand
voltage |
| Power frequency withstand
voltage |
|
| 325 |
450 |
650 |
750 |
| 160 |
260 |
310 |
365 |
|
| Circuit Breaker |
| Type |
| Rated current (A) |
| Rated short-time current (kA) |
| Rated interrupting current
(kA) |
| Rated interrupting time
(cycles) |
| Operating mechanism |
|
| Single-pressure
puffer |
| 1200/1600/2000/3000 |
| 20/31.5/40 |
| 20/31.5/40 |
| 3/5 |
| Spring or
pneumatic |
|
| Disconnecting switch
|
| Type |
| Rated current (A) |
| Rated short-time current (kA) |
| Operating mechanism |
|
| Linear Break |
| 1200/1600/2000/3000 |
| 20/31.5/40 |
| Manual, motor
or pnumatic |
|
| Ground switch |
| Type |
| Rated short-time current (kA) |
| Operating mechanism |
|
| Linear Break |
| 25/31.5/40 |
| Manual,
motor-charged spring, or pneumatic |
|
| Busbar |
| Enclosure |
| Rated current (A) |
| Rated short-time current (kA) |
|
| Three-phase |
| 1200/1600/2000/3000 |
| 20/31.5/40 |
|